Legrand / Raritan / Server Technology Xerus™ JSON-RPC API
|
Public Attributes | |
| boolean | byteSwap |
| 16-bit modbus words should be transferred in big-endian byte order. | |
| string | mask |
| 64-bit unsigned raw mask value as decimal or hexadecimal string, applied before interpreting ("" or "0" = not masked, the same as "0xFFFFFFFFFFFFFFFF") | |
| int | start |
| The least significant bit of the read word used in numerical interpretation. | |
| int | width |
| Word width in bits used in numerical interpretation. | |
Public Attributes inherited from peripheral::GatewaySensorManager::NumericValueEncoding | |
| float | scalingFactor |
| multiply with when interpreting as numeric value | |
| float | offset |
| add value after applying scalingFactor | |
Public Attributes inherited from peripheral::GatewaySensorManager::ValueEncoding | |
| string | encodingId |
| encoding type id | |
| EncodingType | type |
| value coding type | |
| boolean | invertState |
| invert when interpreting as state | |
| vector< InterpretationRule > | interpretationRules |
| error/value interpretation rules | |
| int | minAccessInterval |
| minimum time interval between two read accesses in seconds | |
Definition at line 534 of file GatewaySensorManager.idl.
| boolean peripheral::GatewaySensorManager::ModbusValueEncoding8::byteSwap |
16-bit modbus words should be transferred in big-endian byte order.
For modbus devices that do not comply with this, byteSwap = true must be set. Another application is to use byteSwap to address a single byte in a 16-bit modbus word in case 8-bit values are requested (ModbusValueEncoding8).
Definition at line 541 of file GatewaySensorManager.idl.
| string peripheral::GatewaySensorManager::ModbusValueEncoding8::mask |
64-bit unsigned raw mask value as decimal or hexadecimal string, applied before interpreting ("" or "0" = not masked, the same as "0xFFFFFFFFFFFFFFFF")
Definition at line 546 of file GatewaySensorManager.idl.
| int peripheral::GatewaySensorManager::ModbusValueEncoding8::start |
The least significant bit of the read word used in numerical interpretation.
If start is greater than 0, then one or more least significant bits remain unused. 0 is the default value. For integer values a start > 0 has mostly the same effect as using a mask = ~(2^start-1) and a scalingFactor = 1/2^start.
Definition at line 553 of file GatewaySensorManager.idl.
| int peripheral::GatewaySensorManager::ModbusValueEncoding8::width |
Word width in bits used in numerical interpretation.
If width is smaller than the read word width, then the most significant bits remain unused. 0 is the default value. Example: 24 bit signed integer: ModbusValueEncoding32 with start = 0 and width = 24 and 'type = INT (Only for unsigned integer the use ofmask` would be sufficient.)
Definition at line 562 of file GatewaySensorManager.idl.